Aluminium Conductors Steel Reinforced

TS-EN-50182 (TS-IEC-61089)

TS-EN-50182 (TS-IEC-61089)

Code

Canadian

Standard

Areas

Diameter & No. of Wires

Overall

Diameter

Rated Strength

D.C. Resistance

 Mass per

Unit Length

Type

AWG

Al

Steel

Total

Al

Steel

Core

Conductor

 mm2

No. of Wires

Wire Diameter mm

No. of Wires

Wire

Diameter

mm

mm

kN

Ohm/km

kg/km

17/3

Tuhrus

5

16,83

2,80

19,63

6

1,89

1

1,89

1,89

5,67

665

1,075

68

21/4

Swan

4

21,18

3,53

24,71

6

2,12

1

2,12

2,12

6,36

831

1,355

85,6

27/4

Swallow

3

26,69

4,45

31,14

6

2,38

1

2,38

2,38

7,14

1.023

1,074

107,8

34/6

Sparrow

2

33,59

5,60

39,19

6

2,67

1

2,67

2,67

8,01

1.264

0,854

135,7

42/7

Robin

1

42,41

7,07

49,48

6

3,00

1

3,00

3,00

9,00

1.579

0,677

171,4

54/9

Rawen

1/0

53,52

8,92

62,44

6

3,37

1

3,37

3,37

10,11

1.945

0,536

216,2

67/11

Quail

2/0

67,33

11,22

78,55

6

3,78

1

3,78

3,78

11,34

2.420

0,426

272

85/14

Pigeon

3/0

85,12

14,18

99,30

6

4,25

1

4,25

4,25

12,75

3.035

0,337

343,9

135/7

Waxwing

266800

134,98

7,50

142,48

18

3,09

1

3,09

3,09

15,45

3.220

0,213

430,1

135/22

Partridge

266800

134,87

21,99

156,86

26

2,57

7

2,00

6,00

16,28

5.099

0,214

543,8

152/8

Pheobe

300000

152,09

8,45

160,54

18

3,28

1

3,28

3,28

16,40

3.628

0,189

484,6

152/25

Ostrich

300000

152,19

24,71

174,90

26

2,73

7

2,12

6,36

17,28

5.736

0,190

612,9

242/39

Hawk

477000

241,65

39,19

280,84

26

3,44

7

2,67

8,01

21,77

8.798

0,119

972,8

403/65

Drake

795000

402,56

65,44

468,00

26

4,44

7

3,45

10,35

28,11

14.165

0,072

1621,9

485/63

Cardinal

954000

484,53

62,81

547,34

54

3,38

7

3,38

10,14

30,42

15.589

0,060

1829,8

645/82

Pheasant

127200

645,08

81,71

726,79

54

3,90

19

2,34

11,70

35,10

20.383

0,045

2433,5